RM22TG20
- delivery time60 days
- Quantity
Range of product | Harmony Control Relays |
---|---|
Product or component type | 3-phase control relay |
Relay type | Control relay |
Network number of phases | 3 phases |
Relay name | RM22TG |
Relay monitored parameters | Phase sequence Phase failure detection (2 or more phase cut) |
Time delay type | Without |
Switching capacity in VA | 2000 VA |
Measurement range | 183...528 V voltage AC |
Contacts type and composition | 2 C/O |
Reset time | 1500 ms at maximum voltage |
---|---|
Maximum switching voltage | 250 V AC |
Minimum switching current | 10 mA at 5 V DC |
Maximum switching current | 8 A AC |
[Us] rated supply voltage | 208...480 V AC |
Supply voltage limits | 183…528 V AC |
operating limits | 183...528 V AC |
Power consumption in VA | 15 VA at 480 V AC 60 Hz |
Voltage detection threshold | < 100 V AC |
supply voltage frequency | 50...60 Hz +/- 10 % |
Output contacts | 2 C/O |
run-up delay at power-up | 650 ms |
Response time | <= 200 ms |
Overvoltage category | III conforming to IEC 60664-1 III conforming to UL 508 |
Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
Mounting position | Any position |
Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end |
Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
Housing material | Self-extinguishing plastic |
Status LED | LED (yellow) relay ON LED (green) power ON |
Mounting support | 35 mm DIN rail conforming to IEC 60715 |
Electrical durability | 100000 cycles |
Mechanical durability | 10000000 cycles |
Utilisation category | AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1 |
Safety reliability data | MTTFd = 924.6 years B10d = 850000 |
Contacts material | Cadmium free |
Width | 22.5 mm |
Net weight | 0.09 kg |
Immunity to microbreaks | 10 ms |
---|---|
Electromagnetic compatibility | Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Emission standard for industrial environments conforming to IEC 61000-6-4 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Conducted and radiated emissions class B group 1 conforming to CISPR 11 Conducted and radiated emissions class B conforming to CISPR 22 |
standards | IEC 60255-1 |
product certifications | CE EAC RCM GL CSA UL CCC |
Ambient air temperature for storage | -40…70 °C |
Ambient air temperature for operation | -20…50 °C at 60 Hz -20…60 °C at 50 Hz AC/DC |
Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 |
Pollution degree | 3 conforming to IEC 60664-1 3 conforming to UL 508 |
Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 2.500 cm |
Package 1 Width | 8.200 cm |
Package 1 Length | 9.500 cm |
Package 1 Weight | 103.000 g |
Unit Type of Package 2 | CAR |
Number of Units in Package 2 | 40 |
Package 2 Height | 14.400 cm |
Package 2 Width | 39.600 cm |
Package 2 Length | 29.600 cm |
Package 2 Weight | 4.630 kg |
Unit Type of Package 3 | S02 |
Number of Units in Package 3 | 40 |
Package 3 Height | 15.000 cm |
Package 3 Width | 40.000 cm |
Package 3 Length | 30.000 cm |
Package 3 Weight | 4.855 kg |